About this product
120 Volt, 8 Watt per Foot self-regulating heat trace cable with tinned copper braid and fluoropolymer overjacket. For pipe freeze protection and process temperature maintenance up to 150°F. Cut to length in the field.
2700 Series Self-Regulating Heat Trace
This 120 Volt cable provides pipe freeze protection and process temperature maintenance and can be cut to length in the field. Its self-regulating conductive core produces more heat in colder sections and reduces output as temperature rises.
The 2708-11T00 T construction combines a tinned copper grounding braid with a fluoropolymer overjacket.
Technical Specifications
Heat Output 8 Watt per Foot @ 50°F
Metric Output 26 W/m @ 10°C
Nominal Voltage 120 V
Manufacturer Supply Voltage 110–120 VAC
Cable Type Self-Regulating
Series 2700 Series
Grounding Braid Tinned Copper
Outer Jacket Fluoropolymer Overjacket
Maximum Maintain Temperature 150°F (65°C)
Maximum Intermittent Exposure 185°F (85°C)
Temperature Rating T6
Cut to Length Yes
Field Termination Yes
Cable Overlap Permitted
Ground-Fault Protection Required
Maximum Circuit Length
2708-11T00 — 120 V, 8 W/ft
Maximum circuit length depends on breaker size and minimum startup temperature.
Note: Special consideration must be given for the circuit breaker due to the high initial in-rush currents.
Show allShow less
Voltage Adjustment
Power adjustment factors below apply to the listed 240 V cable types at 208 VAC or 277 VAC.
Construction
Nickel-coated copper bus wires are embedded in an irradiation-crosslinked self-regulating conductive core. A modified-polyolefin inner jacket, tinned-copper grounding braid, and fluoropolymer overjacket complete the cable construction.
2700 Series Cable Selection
Compare the published 2700 Series bulk-cable constructions below. Select a part number to open that product.
TPE Overjacket
Tinned Copper Braid + Fluoropolymer Outer Jacket
Installation Notes
- Cut and terminate in the field using compatible 2700 Series components.
- Use the applicable breaker/circuit-length table.
- Ground the metallic braid.
- Ground-fault equipment protection is required.
Sizing water-pipe freeze protection? Use the Pipe Freeze Protection Configurator.